Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM02990
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 08/13/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) STRAP STUDS IN GARAGE 2) PROVIDE AA TRUSS CALC'S 3) SEAL VAPOR BARRIER IN GARAGE | |
| 08/11/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SEE PREVIOUS INSPECTION 2) SECURE HOLDOWNS, REVIEW ALL DETAILS, TRUSS AA DO NOT MATCH BEARING ON CALC'S | |
| 08/07/2003 | FRAMING | Denied | IVRS - Inspection 0160*/ 1) 3 PT TRUSSES BEARING INCORRECTLY 2) STRAP BEAM AT AZ TRUSS 3) 16" ON CENTER AT GARAGE STUD, INTERIOR BEARING 4) DETAIL 3 A-8B AT GARAGE 5) TC CLIPS AT GARGE 6) DOUBLE TOP PLATE AT GARAGE WALL 7) INSTALL STRAPING AT ALL CORNERS 8) CONTINUE TOP PLATE AT GARAGE GABLE 9) NAIL GARAGE KINGS 10) FIRESTOP SHAFTS NOTE: REVIEW FRAMING, TRUSSES AND MECHANICAL. OK TO CLEAR | |
| 07/29/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) LOAD ROOF PRIOR TO INTERMEDIATES |