Permit: T03CM02975

Parcel: 116275340

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM02975

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/08/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
09/05/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1) ROMEX NOT RATED FOR UNDERGROUND USE. USE UF WHERE RUN UNDERSLAB (KITCHEN).
2) CABLES BUNDLED IN LENGTHS EXCEEDING 24" WILL HAVE TO BE DERATED PER ART 310-15 10-15 CURREN CARRYING CONDUCTORS, CABLES BUNDLED THROUGH LENGTH OF CARPORT TO SERVICE PANEL LOCATION.