Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM02962
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) PLBG FINAL OK. 2) OK FOR C OF O. PENDING ANY OTHER INSP. | |
12/22/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ SEE 719.5 94 UPC CLEAN OUTS EXTENDED TO GRADE UNDER ASPHALT. 2) T&P RELEIF VALVES TO BE GRAVITY DRAIN, - BACKPITCH NOT PERMITTED. 3) REQUIRE A PERMANENT SIGN WITH LEGIBLE WORDS " THIS BLDG HAS NON-METALLIC INTERIOR WATER PIPING", FASTENED ON OR INSIDE THE MAIN ELECTRIC SERVICE PANEL. 4) INSPECTION STOPPED. |