Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/06/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) 2" CABLE CONNECTOR NOT LISTED FOR MULTIPLE HOME RUN CABLE TERMINATION. TO BE USED PER LISTING. 2) SINGLE GANG EXTERIOR WALL BOXES CANNOT HAVE 16P NAILS THRU THEM FOR SUPPORT. USE PROPER BOXES. SEE 110-3B, 300-15A, 110-12. PLEASE LEAVE PHONE NUMBER AND NAME OF LICENSED CONTRACTOR DOING WORK. |
| 09/29/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: ROMEX MUST BE TERMINATED WITH LISTED CLAMP-TYPE CONNECTORS IN PANELS, EXHAUST FANS, AND METAL 4/0 BOXES PER NEC, PUSH-IN PLASTIC BUSHINGS NOT APPROVED. SEE 370.17 NEC, 315(A) |