Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03CM02961
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1107AM | |
| 11/04/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0935*/ SEE # 330 | |
| 10/30/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0245*/ 1) REVISED PLAN TO BE APPROVED BY PLAN CK FOR CHANGE OF SERVICE DESIGN, PER LAST INSP. WRITE UP. 2) BOND UFER SYSTEM TO NUETRAL BUSS, SEE DIAGRAM BEHIND COVER OF ENCLOSURE. 3) NEED TO VERIFY WATER BONDING IF NOT POLY PIPE. | |
| 10/24/2003 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PLANS ARE NOT REFLECTIVE OF SERVICE PLEASE REVISE PLANS OR INSTALL AS PER PLANS 2) PLEASE PROVIDE ? FOR OVER HEAD SERVICE 3) NO PERMANENT METAL ADDRESS LABEL | |
| 10/17/2003 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000* |