Permit: T03CM02961

Parcel: 12006012A


Addresses:

3810 S 2ND AV #01


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T03CM02961

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*SENT TO TEP ON 1107AM
11/04/2003 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0935*/ SEE # 330
10/30/2003 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*/ 1) REVISED PLAN TO BE APPROVED BY PLAN CK FOR CHANGE OF SERVICE DESIGN, PER LAST INSP. WRITE UP. 2) BOND UFER SYSTEM TO NUETRAL BUSS, SEE DIAGRAM BEHIND COVER OF ENCLOSURE. 3) NEED TO VERIFY WATER BONDING IF NOT POLY PIPE.
10/24/2003 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*/ 1) PLANS ARE NOT REFLECTIVE OF SERVICE PLEASE REVISE PLANS OR INSTALL AS PER PLANS 2) PLEASE PROVIDE ? FOR OVER HEAD SERVICE 3) NO PERMANENT METAL ADDRESS LABEL
10/17/2003 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*