Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM02959
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/1) WASTE AND VENT SYSTEM IS OK. 2) OVERHEAD WATER DISTRIBUTION. 3) GAS PRESSURE TEST IS OK. | |
10/06/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/1) MUST RUN 1-1/2" TRAP ARM ALL THE WAY TO BARREL OF 3" STACK. 2) MUST SEPARATE HOT AND COLD WITH INSULATION. 3) MUST REMOVE ALL THREAD PROTECTORS IN GAS LINE. 4) RE-TEST SYSTEM. | |
09/29/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/1) MUST PROVIDE WATER TEST ON WASTE AND VENT SYSTEM ALL THE WAY TO TOP OF VENT THRU ROOF.2) I DO NOT ACCEPT COPPER BACKING WITH TIE WIRE FOR TUB DIVERTERS. 3) CAN NOT HAVE A 2" TRAP ARM FOR LAVATORY . MAX TRAP AND TRAP ARM IS 1-1/2". 4) STRAP DOWN GAS LINE EVERY 6'. 5) REMOVE THREAD PROTECTOR AND PROVIDE APPROVED COUPLING. |