Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM02959
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
10/06/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*/ NOTES: 1) 2" CABLE CONNECTOR NOT LISTED FOR MULTIPLE HOME RUN CABLE TERMINATION. TO BE USED PER LISTING. 2) SINGLE GANG EXTERIOR WALL BOXES CANNOT HAVE 16 P NAILS THRU THEM FOR SUPPORT. USE PROPER BOXES. SEE 110-3B, 300-15A, 110-12. | |
09/29/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*/ 1) SEE WRITE-UP FOR #324 |