Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02954
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/11/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTABLE SURFACES. 2) EMERGENCY TEST SWITCH TO BE BELOW CEILING TILES TO BE VISIBLE. 3) TIGHTEN LOOSE SEALTITE FITTINGS. 4) BONDING JUMPER ON SUPPLY SIDE TO BE AS PER 250-101 AND 250-66 ALSO BOND GUTTER. 5) BONDING DEVICES NEEDED AT ALL NIPPLE POINTS BEFORE 1ST DISCONNECT. OK 2X4'S FOR LIGHTING. |