Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM02932

Parcel: 137313690

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
08/08/2003 ELECTRIC - UFER Approved IVRS - Inspection 0000*
07/07/2003 ELECTRIC - UFER Denied IVRS - Inspection 0999* 1) NO UFER INSTALLED. MUST BE CONNECTED TO 20 FT LENGTH OF REBAR 3" ABOVE SOIL
07/02/2003 ELECTRIC - UFER Denied IVRS - Inspection 0950*