Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM02902
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR C OF O. | |
09/24/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*.1) PROVIDE INSTALLATION INSTRUCTIONS FOR PATIO HEATERS. 2) SECURE LOW VOLTAGE WIRING TO CONDENSORS. 3) RELOCATE REFER LINES FROM BLOCKING ACCESS TO DECK AND SECURE TO DECK. 4) GREASE DUCT SHAFT MUST BE VENTILATED AT ROOF PENETRATION, COUNTER FLASHING OR ROOF CAP ON CURB SHOULD BE WELDED TO THE GREASE DUCT TO MAINTAIN WEATHER PROTECTION. CLEANOUT OPENINGS IN GREASE DUCT ON ROOF NOT TO CODE. SEE SECTION 506.3.9 2000 IMC. | |
09/15/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK FOR TEMP C OF O. 1) PROVIDE ANGLE IRON AROUND FIRE DAMPER. PROVIDE ACCESS DOOR IN DUCT. LABEL AS NECCESARY. 2) PROVIDE CONDENSATE DRAIN LINES IN WALK IN COOLERS. 3) PAINT EXPOSED GREASE DUCT ON ROOF. 4) PROVIDE CLEAN OUT ACCESS DOORS ON GREASE DUCT ON ROOF. 5) PERMANENTLY LABEL FAN COILS AND CONDENSORS. SECURE LOW VOLTAGE WIRE AT CONDENSORS. 6) SECURE REFER LINES AT 5 TON CONDENSORS. 7) RELOCATE GAS LINE AND ELECTRIC CONDUIT BLOCKING EVAP. COOLER. |