Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/26/2003 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* SHEET ROCK OK TO COVER SOFFITS & CEILINGS. 2) 2 HR SEPARATION FROM 2ND FLOOR TO 1ST FLOOR REDUCED TO 1 HR 4" CONSRETE OK. 3) 2 HR DEMISE REDUSED TO 1 HR PER 302.3.3.1 ( SEE ATTATTACHED RFI) |
| 08/21/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* 1) DO NOT COVER SOLLITS UNTIL MONOKOTE REPAIRED (EXCEPT IN ARESAS WHERE THERE IS NO MONOKOTE.) 2) DO NOT TAPE AROUND PENETRATIONS IN FIRE WALL UNTIL FIRE STOP INSPECTION IS COMPLETE. 3) PROVIDE APPROVED REVISION REDUCING 2 HOUR WALL TO 1 HOUR. |