Permit: T03CM02899

Parcel: 128100800

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM02899

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O.
09/19/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ PROVIDE ELECTRIC CIRCUIT AND DISCONNECT SWITCH FOR WALK IN FAN COILS. CUT OFF SECTION OF EXHAUST DUCT EXTENDING INTO TYPE 2 HOOD. NEED TO SEE EQUIPMENT ON ROOF. CLAMP LOW VOLTAGE WIRE WITH NYLON TIE STRAPS NOT DUCT TAPE. RECALL FOR INSPECTION. OK FOR C OF O.
09/18/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/1) PROVIDE FUSES IN ELEC. DISCONNECTS. 2) STRAP UP LINE SET IN FRONT OF DISCONNECT. SUPPORT CONDENSATE DRAIN LINE. INSULATE SUCTION LINE ALL THE WAY TO FAN COIL. PROVIDE BUSHINGS WHERE REFER LINES PENETRATE CABINET OF FAN COILS. 3) NEED TO SEE WALK-IN COOLER FAN COILS AND RELATED PIPING.
09/17/2003 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*/TERMINATE SECONDARY CONDENSATE TO A CONSPICUOUS LOCATION. SUPPORT CONDENSATE DRAIN LINES IN ATTIC. FINISH EXHAUST DUCTING AND RETURN AIR IN KITCHEN. STILL NEED TO SEE WALK IN FAN COILS AND CONDENSORS. WILL CHECK REMAINING CORRECTIONS ON FINAL. LABEL FAN COILS AND CONDENSORS.