Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02899
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
09/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/1) NORTH WALK-IN UNIT REQUIRES A DISCONNECTING MEANS WITHIN SIGHT. 2) ILLUMINATION REQUIRED ABOVE WALK-INS IN CONCEALED AREA. 3) MAINTENANCE RECEPTACLE REQUIRED AT EACH. | |
09/22/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK TEMP POWER AND FUEL TEST. | |
09/18/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ CORRECTIONS: 1) CHECK THE SIEMENS TRANSFORMER INSTALLATION INSTRUCTIONS TO SEE IF AN EMBERS PLATE IS REQUIRED BENEATH THE TRANSFORMER. 2) THE WATER HEATER DISCONNECT DOES NOT HAVE THE REQUIRED CLEARANCES. 3) ALL DISCONNECTS NEED TO BE MARKED WITH THE PANEL NAME AND CIRCUIT NUMBERS. FOR INTERIOR MTL A "MAGIC MARKER" WILL DO. FOR EXTERIOR MTD USE METALLIC EMBOSSED STRIP. 4) BE SURE ALL EBO AND EXIT LIGHTS ARE CHARGED AND OPERABLE. AN ACTIVE DEMONSTRATION IS REQUIRED. 5) ALL EQUIPMENT SHOULD BE SET IN PLACE, PLUGGED IN, AND OPERABLE. RECALL. | |
09/15/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |