Permit: T03CM02899

Parcel: 128100800

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM02899

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*/ OK FOR C OF O.
09/25/2003 BUILDING - FINAL Denied IVRS - Inspection 0999* 1) PROVIDE FINALS FROM OTHER INSPECTORS. 2) PROVIDE ACCESS FOR INSP OF WALL ABOVE CEILING. 3) YOU DO NOT HAVE A C/O DO NOT OCCUPY.
09/24/2003 BUILDING - FINAL Denied IVRS - Inspection 0999* IMPROPER FIRE STOP ON CORRIDOR WALL
09/22/2003 BUILDING - FINAL Denied IVRS - Inspection 0999* 1) SEE INSP FROM 9/15/03. 2) ACCESSIBLE BATHROOMS REQUIRE SIGNAGE MEETING ARTICLE 4.30 OF A.D.A.A.G. a) RAISED CHARACTERS & PIETO GRAMS 4.30.4 b) NON GLARE FINISH 4.30.5 c) SYMBOL OF ACCESSIBILLITY REQUIRED 4.30.7
3) SIGN OVER FRONT DOOR "THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED." 4) RELOCATE PAPER TOWEL DISPENSERS OUT OF ACCESSIBLE PATH. 5) PROVIDE APPROVED FINALS FROM ALL TRADES.
09/17/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*