Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 08/12/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER REGARDING FIXTURE CHANGES 2) FIXTURES TO BE ATTACHED TO GRID 410.16 3) A SUPPORT WIRE IS NEEDED FOR EXIT SIGNS 4) TIGHTEN LOOSE FITTINGS 5) ELECTRIC TO BE INDEPENDENTLY SUPPORTED-NOT ON " ? WIRES " 300.11 6) WHERE BOXES ARE MORE THAN 1/4" FROM BOX TO SURFACE AN APPROVED EXTENDER RING IS NEEDED 370.20 7) M/C CABLE TO BE TERMINATED TO CONDUIT 8) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS 200.7 AND 210.5 |