Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM02895

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
08/12/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER REGARDING FIXTURE CHANGES 2) FIXTURES TO BE ATTACHED TO GRID 410.16 3) A SUPPORT WIRE IS NEEDED FOR EXIT SIGNS 4) TIGHTEN LOOSE FITTINGS 5) ELECTRIC TO BE INDEPENDENTLY SUPPORTED-NOT ON " ? WIRES " 300.11 6) WHERE BOXES ARE MORE THAN 1/4" FROM BOX TO SURFACE AN APPROVED EXTENDER RING IS NEEDED 370.20 7) M/C CABLE TO BE TERMINATED TO CONDUIT 8) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS 200.7 AND 210.5