Permit: T03CM02865

Parcel: 140321250

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/25/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
09/23/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) BRACE TRUSSES PER CALC'S 2) CHECK PERIMETER NAILING 3) 3 POINT BEARING TRUSSES NOT BEARING ON DOUBLE TOP PLATE DETAIL 3/D2 4) COMPLY WITH DETAIL 2/D2 5) ROOF TO WET TO WALK 6) BEAM TO POST CONNECTION NOT PER PLAN 7) WIND BRACE REQUIRES 2 NAILS AT EACH END 8) NAIL PROTECT PLUMBING 9) SEE NOTE ON FRAMING PLAN FOR DTC CLIP INSTALLATION
09/19/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) WIND BRACE REQUIRES 2 NAILS AT EACH END 2) NAIL PROTECT PLUMBING AND ELECTRIC FROM OUTSIDE 3) SHEAR TRANSFER NOT NAILED PER PLAN 4) STRAP CORNERS THAT ARE NOT CABIN TIED 5) STOPPED INSPECTION TO MANY ITEMS RECALL WHEN READY