Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T03CM02822
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2004 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
04/01/2004 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) NO ADDRESS ON HOUSE 2) INCORRECT COLOR CODE ON WIRES, WHITE WIRES NOT ALLOWED TO BE HOT 3) ANTI-CORROSIVE COMPOUND REQUIRED ON ALUMINUM CONDUCTORS 4) OPEN KNOCK OUTS 5) NON WATER BOND LABEL MISSING 6) GROUND SUB PANEL 7) UNDER SLAB GAS LINE IMPROPERLY SLEVED AND VENTED 8) WATER HEATER MUST BE REMOVABLE WITHOUT REMOVING FURNACE 9) FURNACE 'B' VENT PLUGGED WITH TAPE 10) MASTER BATH CONVENIENCE OUTLET MUST BE GFCI 11) HALL BATH NOT COMPLETE | |
03/31/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) RECALL NOT READY ON SECOND STOP | |
03/29/2004 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PAINT PLASTIC ON ROOF 2) SECURE FLEX (SUPPORT) WITHIN 12" OF HACR BOXES AT A/C 3) INSTALL DRIP LEG AT FURNACES 4) FLEX NOT APPROVED AT TPRS 5) SUPPORT CONDENSATE AND INSTALL TURN-DOWN 6) A/C OVER FUSED 7) 3-SCREW FLUES 8) EXPOSED ELECTRICAL IN FURNACE/WATER HEATER ROOM 9) COMPLETE GRADING 10) RECALL-NOT READY 11) STOPPED INSPECTION AT GARAGE |