Permit: T03CM02822

Parcel: 116276960

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM02822

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
04/01/2004 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) NO ADDRESS ON HOUSE 2) INCORRECT COLOR CODE ON WIRES, WHITE WIRES NOT ALLOWED TO BE HOT 3) ANTI-CORROSIVE COMPOUND REQUIRED ON ALUMINUM CONDUCTORS 4) OPEN KNOCK OUTS 5) NON WATER BOND LABEL MISSING 6) GROUND SUB PANEL 7) UNDER SLAB GAS LINE IMPROPERLY SLEVED AND VENTED 8) WATER HEATER MUST BE REMOVABLE WITHOUT REMOVING FURNACE 9) FURNACE 'B' VENT PLUGGED WITH TAPE 10) MASTER BATH CONVENIENCE OUTLET MUST BE GFCI 11) HALL BATH NOT COMPLETE
03/31/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) RECALL NOT READY ON SECOND STOP
03/29/2004 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) PAINT PLASTIC ON ROOF 2) SECURE FLEX (SUPPORT) WITHIN 12" OF HACR BOXES AT A/C 3) INSTALL DRIP LEG AT FURNACES 4) FLEX NOT APPROVED AT TPRS 5) SUPPORT CONDENSATE AND INSTALL TURN-DOWN 6) A/C OVER FUSED 7) 3-SCREW FLUES 8) EXPOSED ELECTRICAL IN FURNACE/WATER HEATER ROOM 9) COMPLETE GRADING 10) RECALL-NOT READY 11) STOPPED INSPECTION AT GARAGE