Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2003 |
MECHANICAL - HOODS |
|
Approved |
|
| 11/20/2003 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CANNOT DUCT ALUMINUM EXH. BLOWERS. BLOWERS WERE NOT LISTED FOR DUCTING. 2) CONDENSATE DRAINS - PVC NEEDS TO BE PAINTED. OPEN TEE FOLLOWS TRAPS, NOT AHEAD OF TRAP. |
| 11/18/2003 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/13/2003 |
MECHANICAL - HOODS |
|
Denied |
IVRS - Inspection 0999*/ NO ACCESS TO DINING ROOM - BLOCKED OFF. - ADVISED OWNER ON 11/05/03 INSP. THAT I WANTED TO MEET MECH. CONTR. ON JOB. PLEASE ARRANGE THIS. WANT ADDITIONAL DUCT TRAPEZING ON LARGE DUCTS. THIS IS NECESSARY BEFORE CEILING TILES CAN BE COVERED. |