Permit: T03CM02817

Parcel: 10408051B


Addresses:

4565 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T03CM02817

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2003 MECHANICAL - HOODS Approved
11/20/2003 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*/ 1) CANNOT DUCT ALUMINUM EXH. BLOWERS. BLOWERS WERE NOT LISTED FOR DUCTING. 2) CONDENSATE DRAINS - PVC NEEDS TO BE PAINTED. OPEN TEE FOLLOWS TRAPS, NOT AHEAD OF TRAP.
11/18/2003 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*
11/13/2003 MECHANICAL - HOODS Denied IVRS - Inspection 0999*/ NO ACCESS TO DINING ROOM - BLOCKED OFF. - ADVISED OWNER ON 11/05/03 INSP. THAT I WANTED TO MEET MECH. CONTR. ON JOB. PLEASE ARRANGE THIS. WANT ADDITIONAL DUCT TRAPEZING ON LARGE DUCTS. THIS IS NECESSARY BEFORE CEILING TILES CAN BE COVERED.