Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/02/2003 |
PLUMBING - FINAL |
|
Approved |
|
| 12/01/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) SOAP DISPENSERS REQUIRE BACKFLOW PROTECTION. NOTE: DO NOT USE VACCUM BREAKER 2) INDIRECT WASTE PIPING LESS THAN 5 FEET DOES NOT NEED USE APP. MAT'L TRAP OR VENT. BETWEEN 5' AND 15' MUST BE DIRECTLY TRAPPED SUPPORT ALL INDIRECT WASTE PIPING 3) CAULK ALL FIXTURES 4) DRAIN ON 007 NOT RUN |