Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*/ 1) RECEIVED REVISED WASTE RISER DIAGRAM FOR ADDITIONAL FLOOR SINK. 2) OK TO COVER. |
| 09/07/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) ADDTIONAL FLOOR SINK NOT ON APPROVED PLAN 2) S.S. TRENCH DRAIN NOT SECURED TO TAIL PIECE |
| 09/02/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/1) N/H UNDERGROUND DWV OK ABS DWV UG OK WATER TEST OK. 2) OK TO COVER CONTRACTOR TO ENSURE TEST ON 2" FLOOR DRAIN IN MECH. RM. 3) NEED TO SEE FLOOR SINKS AND DRAINS PRE-POUR. |