Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 07/22/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0160*/ 1) SEE PREVIOUS INSPECTION-ITEMS ONE AND FOUR IN FRAMING 2) SEE PREVIOUS INSPECTION-ITEMS ONE AND TWO IN MECHANICAL STRAP PLATE (TOP) AT WATER HEATER STAND |
| 07/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0160*/ 1) DOUBLE STUD OR STUD SHOE ALL OVERNOTCHED 2) STRAP WALLS NEAR ENTRY 3) BLOCK #3 SHEAR 4) SECURE ALL AB'S 5) INSTALL 220V 6) REPAIR BROKEN J-BOX IN KITCHEN 7) REPAIR TORN DUCTS 8) SUPPORT DUCTS PER CODE 8) BLOCK VENT IN KITCHEN |
| 07/18/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |