Permit: T03CM02808

Parcel: 12701008A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM02808

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR FINAL C OF O.
02/11/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999* OK FOR TEMP C OF O / 1) GAS FLEX CONNECTOR NOT ADEQUATE FOR 399,000 BTU BOILER. 2) PERMANENTLY LABEL ALL EQUIPMENT WITH SUITE NUMBER AND UNIT NUMBER. 3) GAS FLEX NOT ADEQUATE FOR THE TWO LARGE UNITS ON ROOF. - 5 TON - 35/40 - 11 TON - 59/70 - 16 TON - 82/110.