Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM02808
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR FINAL C OF O. | |
02/11/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* OK FOR TEMP C OF O / 1) GAS FLEX CONNECTOR NOT ADEQUATE FOR 399,000 BTU BOILER. 2) PERMANENTLY LABEL ALL EQUIPMENT WITH SUITE NUMBER AND UNIT NUMBER. 3) GAS FLEX NOT ADEQUATE FOR THE TWO LARGE UNITS ON ROOF. - 5 TON - 35/40 - 11 TON - 59/70 - 16 TON - 82/110. |