Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T03CM02808
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2004 | MECHANICAL - HOODS | Approved | IVRS - Inspection 0000*/ 1) INSPECTED FINAL FIRE WRAP-OK TO COVER | |
01/22/2004 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*/ INSPECTED MAKE UP AIR DUCT. OK TO SHEET ROCK CEILING | |
01/21/2004 | MECHANICAL - HOODS | Denied | IVRS - Inspection 0999*/ BANDING ON FIRE WRAP NOT PER MANUFACTURERS SPECS. READ THE INSTRUCTIONS. BANDS ALSO NEED TO BE TIGHTER. | |
01/16/2004 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*/ INSPECTED GREASE DUCTS AGAIN. OK TO FIRE WRAP. INSPECTED ALL DUCT ABOVE CEILING. OK FOR CEILING TILES. | |
12/29/2003 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*/ INSPECTION ON GREASE DUCTS. OK TO FIRE WRAP. BE SURE TO EXTEND WRAP ALL THE WAY TO TOP OF DUCT AS PER 2000 IMC. IF LANDING IS DIFFICULT AT TOP TAPERED SECTION. USE PINS AS PER MANUFACTURERS INSTRUCTIONS. |