Permit: T03CM02808

Parcel: 12701008A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM02808

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/11/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ OK TEMP C OF O.
02/04/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) SIGN OVER DOOR ENCLOSURER TO BE BONDED 600.9 2) NEED MARKING LABEL 600.4
02/02/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) AN APPROVED EXTENDER RING IS NEEDED IF BOX IS MORE THAN ΒΌ" IN NON COMBUSTABLE 320.20. 2) FILL UNUSED OPENINGS IN BOXES. 3) WHERE IS VIEW SIGNS LISTING AND MARKINGS PER 600.3 & 600.4. 4) SUPPORT WIRES NEEDED FOR TRAC LIGHTS - 1 PER TRAC. 5) MAINTAIN CLEARANCE TO ICE MACHINE DISCONNECT. 6) TIGHTEN LOOSE SEALTITE FITTINGS. 7) PROTECT SEALTITE FROM SHARP METAL EDGES. 8) ISOLATE PRIMARY CONDUCTORS TO A/C UNIT UP TO SWITCH.
01/27/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK TEMP POWER ER TEST
SENT TO TEP ON 1/28/04
01/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ OK TO TILE EXCEPT AS NOTED. NEED TO SEE TRAC LIGHTING CONNECTORS.