Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/11/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ OK TEMP C OF O. | |
| 02/04/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) SIGN OVER DOOR ENCLOSURER TO BE BONDED 600.9 2) NEED MARKING LABEL 600.4 | |
| 02/02/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) AN APPROVED EXTENDER RING IS NEEDED IF BOX IS MORE THAN ΒΌ" IN NON COMBUSTABLE 320.20. 2) FILL UNUSED OPENINGS IN BOXES. 3) WHERE IS VIEW SIGNS LISTING AND MARKINGS PER 600.3 & 600.4. 4) SUPPORT WIRES NEEDED FOR TRAC LIGHTS - 1 PER TRAC. 5) MAINTAIN CLEARANCE TO ICE MACHINE DISCONNECT. 6) TIGHTEN LOOSE SEALTITE FITTINGS. 7) PROTECT SEALTITE FROM SHARP METAL EDGES. 8) ISOLATE PRIMARY CONDUCTORS TO A/C UNIT UP TO SWITCH. | |
| 01/27/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) OK TEMP POWER ER TEST SENT TO TEP ON 1/28/04 |
|
| 01/16/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK TO TILE EXCEPT AS NOTED. NEED TO SEE TRAC LIGHTING CONNECTORS. |