Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM02774
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK 2) CERTIFICATIONS ON FILE WITH TUCSON WATER 3) OK FOR C OF O PENDING ANY OTHER INSPECTION | |
10/23/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PLEASE PROVIDE CORRECT AIR GAP AND TERMINATION OF PIPING AT FLOOR SINK IN COFFEE BAR AREA. 2) PLEASE HAVE RPB CERTIFICATION COMPLETED. | |
10/21/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) WATER HEATER REQUIRES PAN AND DRAIN. 2) INDIRECT WASTE PIPING BETWEEN 5-15' REQUIRES A TRAP. 3) EACH WATER OPERATED PEICE OF EQUIPMENT REQUIRES ITS OWN REDUCED PRESSURE AND OR BACKFLOW DEVICE. 4) PROVIDE CERTIFICATION ON BACKFLOW PREVENTORS. | |
10/06/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/THIS INSPECTION IS FOR TEMP. POWER FOR TESTING (NO CODE) APPROVED. |