Permit: T03CM02774

Parcel: 117121280


Addresses:

135 E CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM02774

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) PLANS HAVE TO BE REVISED, APPROVED PLANS SHOW A 120/208 V SYSTEM, HOWEVER A 120/240 V. STINGER LEG SYSTEM ON SITE USED SER. LAYOUT AND LOADS WILL BE DIFFERANT, OBTAIN APPROVED REVISED PLANS. 2) MISSING FIXTURES AT FRONT. 3) MISSING FRONT COUNTER 220V. RECEPTACLE. 4) LABEL PANELS AND INSTALL SCHEDULES - OUTSIDE LABEL 120/240V SYSTEM BLDG LEG. 5) REMOVE OLD TEMP WIRING AND SERVICE.
10/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ TEMP POWER IS APPROVED. NO BOND HAS BEEN POSTED YET.