Permit: T03CM02765

Parcel: 11010298A


Addresses:

3150 N SWAN RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM02765

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ OK FOR FINAL C OF O.
05/19/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ PROVIDE OUTSIDE AIR INTAKES. SECURE MAKE UP AIR DUCT IN EQUIPMENT ROOM AND SECURE EXHAUST DUCT. NEED TO SEE DUCT SMOKE DETECTOR. PROVIDE ACCESS TO FIRE DAMPER IN CEILING AND REMOVEABLE BAND ON FLEX DUCT.
04/09/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ INSPECTED FIRE DAMPER AND CONDENSATE. OK FOR CEILING TILES. STILL NEED TO SEE ROOF TOP AND DUCT SMOKE DETECTOR.