Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM02765
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ OK FOR FINAL C OF O. | |
| 05/19/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ PROVIDE OUTSIDE AIR INTAKES. SECURE MAKE UP AIR DUCT IN EQUIPMENT ROOM AND SECURE EXHAUST DUCT. NEED TO SEE DUCT SMOKE DETECTOR. PROVIDE ACCESS TO FIRE DAMPER IN CEILING AND REMOVEABLE BAND ON FLEX DUCT. |
|
| 04/09/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ INSPECTED FIRE DAMPER AND CONDENSATE. OK FOR CEILING TILES. STILL NEED TO SEE ROOF TOP AND DUCT SMOKE DETECTOR. |