Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02765
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/10/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ UL TESTING IN PROGRESS. UPON COMPLETEION A FIELD LABEL WILL BE ISSUED AND FIELD REPORTS SENT OUT - CITY OF TUCSON WOULD LIKE A COPY FOR RECORDS. INSP. WITNESSED FIELLD TESTING IN PROGRESS. | |
| 05/25/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ GERERATOR HAS BEEN TESTED FOR OPERATIONS. OK TEMP C OF O. PLEASE PROVIDE 3RD PARTY CERTIFICATION - FIELD REPORT FOR GENERATOR. | |
| 05/24/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ CANCELLED BY ALEX. | |
| 05/21/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/20/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) OK TEMP C OF O FOR OFFICE SET-UP AND MEDICAL EQUIPMENT STOCKING 2) FINISH ITEMS #2, 3 AND 6 AS DISCUSSED 3) NEED TO CHECK MEDICAL EQUIPMENT FOR LISTING | |
| 05/19/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) INSULATED POWER PANELS TO HAVE BREAKERS LABELED AS TO LOCATION. 2) INSTALL EXAM LIGHTS AS TO MANUFACTURERS INSTRUCTIONS. PLEASE PROVIDE A SET FOR REVIEW. 3) X-RAY EQUIPMENT NOT TERMINATED. 4) CLEAN OUT TRASH FROM FLOOR BOXES AND ADJUST TO FLUSH. 5) LOOSE FITTINGS - LOCK NUT BACKWARDS - USE APPROVED FITTINGS. 6) FINISH ITEMS 2 AND 6 FROM PREVIOUS INSP. |
|
| 04/22/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) LABEL ISOLATE POWER PANELS 2) LABELING NEEDED PER 700.8 3) FINISH LIGHTING/EXAM LIGHTS 4) FINISH FLOOR BOXES 5) CHECK ROOF NEXT TIME 6) PLEASE VERIFY LISTING ON GAS MANIFOLDS, GENERAL ? SET AND MEDICAL EQUIPMENT 7) OK DEVICES |