Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/18/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK C OF O | |
03/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) WIRING TO BE AS PER 517.13. 2) CORDS NOT ALLOWED ABOVE CEILING 400.7 AND 400.8. 3) WHERE IS JUNCTION BOX FOR SIGN LIGHTS? | |
02/20/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL FINAL OK-WAS APPROVED FOR TEMP C OF O 2/19/04 | |
02/19/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ ONCE EXAM LIGHTS ARE INSTALLED CAN FINAL. OK FOR TEMP C OF O. | |
02/17/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) CLOSET CAN TO BE INSTALL 6" FROM EDGE OF SHELF 410.8 2) PLEASE PROVIDE AN ADDRESS LABEL ON OUTSIDE COVER/DOOR OF SERVICE 3) PLEASE PROVIDE A LETTER FOR POLE MAKE UP 4) NEED TO SEE CONNECTIONS FOR EXAM LIGHTS |