Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/18/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK C OF O |
| 03/12/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) WIRING TO BE AS PER 517.13. 2) CORDS NOT ALLOWED ABOVE CEILING 400.7 AND 400.8. 3) WHERE IS JUNCTION BOX FOR SIGN LIGHTS? |
| 02/20/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PARTIAL FINAL OK-WAS APPROVED FOR TEMP C OF O 2/19/04 |
| 02/19/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ ONCE EXAM LIGHTS ARE INSTALLED CAN FINAL. OK FOR TEMP C OF O. |
| 02/17/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CLOSET CAN TO BE INSTALL 6" FROM EDGE OF SHELF 410.8 2) PLEASE PROVIDE AN ADDRESS LABEL ON OUTSIDE COVER/DOOR OF SERVICE 3) PLEASE PROVIDE A LETTER FOR POLE MAKE UP 4) NEED TO SEE CONNECTIONS FOR EXAM LIGHTS |