Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM02752
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2003 | ELECTRIC - INTERMEDIATE | Approved | 1) OK WALLS | |
12/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK WALL ROOM # 103, 142, 143, 106 - 115, 118, 185. | |
12/22/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
12/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS ROOM #121-123, 125, 127, 160 AND 161 | |
12/17/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER AUTHORIZING M/C CABLE AND FLEX CONDUIT OVER 72" 2) OK ROOM #116, 117, 119, 120, 126-128, 130-133 ANF 162 FOR WALLS | |
12/12/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) RACEWAY NOT TO BE SUPPORTED OFF OF ANOTHER RACEWAY 2) FILL UNUSED OPENINGS 3) TIGHTEN LOOSE FITTINGS 4) SUPPORT CONDUITS AS PER CODE | |
12/05/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK 4-4" PVC XFMR AT BLDG 2) OK CNAS IN EXTERIOR SOFFITS SUBJECT TO VERIFICATION OF USE FOR FLEX CONDUIT | |
11/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK 8 POLE BASE BONDING TO CONDUITS-PLEASE CALL FOR POLE HEAD INSPECTION BEFORE STANDING 2) MEET WITH CONTRACTOR TO DISCUSS PANEL CLEARANCES | |
10/02/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE ADD 02010 TO PERMIT 2) ALL CONDUITS INSTALLED FOR PATIENT CARE ARE TO BE AS PER 517 3) OK PVC CONDUITS EXCEPT AS NOTED |