Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/15/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : 1) EACH ELECTRIC SERVICE PANEL TO BE LABELED " THIS BLDG HAS NON METALLIC WATER PIPING". 2) ALL EXTERIOR CLEAN -OUTS TO BE CUT TO GRADE W? CLEANOUT ADPT. PLUGS. 3) UNIT #1 EXPANSION IN TANK STILL NOT SUPPORTED. YOU SHOULD PAY A RE-INSPECTION FEE-NEXT TIME. |
|
| 09/10/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) UNIT THREE STILL LOCKED 2) CLEAN-OUTS HAVE NOT BEE CUT DOWN 3) NUMBER ? WATER HEATER REQUIRES DIELECTRIC ISOLATION. EXPANSION TANK NOT ADEQUATELY SECURED |
|
| 09/08/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)UNIT NUMBER ONE WATER GEATER HOOKED UP BACKWARDS. 2)UNIT NUMBER THREE NO ACCESS 3)CLEANOUTS TO BE CUT TO GRADE 4)"THIS BUILDING HAS NON-METALLIC WATER PIPING" INSTALLED IN ELECTRIC SERVICE PANEL |