Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T03CM02738
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2004 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :*APPROVED. (1) #100 BATHROOM CUT IN BOX NOT TERMINIATED OR WIRE NUT, SECURE BOX. (2) ADDRESS LIGHT AT TOP OF STAIRS IN #102. HAVE ELECTI????? ADDRESS #1 & 2. OK FOR TEMP POWER SUBJECT TO BOND & OTHER INSPECTORS SIGN OFF. (3) PLEASE INSURE THERE WILL NOT BE TV OR PHONE BOXERS BELOW SERVICES THIS WILL STOP FINAL ELECT THERE ARE TV & CA CABLES AND CONDUITS UNDER SERVICES. (4) THIS PERMIT IS TO HAVE UNITS #100, #101, #102 AND #103 ON IT PRIOR TO CLEARANC3. |