Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/16/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/15/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0935* |
| 07/11/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*/1) M/C CABLE TO BE SUPPORTED AS PER CODE- NOT TO FACIT OTHER, NOT IN LARGE LOOPS, NOT ON CEILING GRID WIRES, NOT OFF OF SPRINKLER PIPE. |
| 07/08/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* 1)PROPERLY SUPPORT M/C CABLE WITH IN 12" OF BOX AND EVERY 6' AS PER CODE 334-10. 2) PREVENT DIE-ELECTRIC CONTACT WITH COPPER PIPING. 3) INSTALL ALL BOX COVERS. |
| 06/27/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* |