Permit: T03CM02733

Parcel: 13316031C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/31/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/16/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
07/15/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*
07/11/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/1) M/C CABLE TO BE SUPPORTED AS PER CODE- NOT TO FACIT OTHER, NOT IN LARGE LOOPS, NOT ON CEILING GRID WIRES, NOT OFF OF SPRINKLER PIPE.
07/08/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* 1)PROPERLY SUPPORT M/C CABLE WITH IN 12" OF BOX AND EVERY 6' AS PER CODE 334-10. 2) PREVENT DIE-ELECTRIC CONTACT WITH COPPER PIPING. 3) INSTALL ALL BOX COVERS.
06/27/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*