Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/16/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK RECEPTION COUNTER WALL 2) OK ABOVE CEILING PHASE 1 |
| 07/15/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0935*/ 1) NO WORK PROGRESS-A REFEE HAS BEEN ASSESSED 2) WALL ELECTRIC NOT SUPPORTED |
| 06/30/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK WALLS PHASE ONE-EAST HALF |
| 06/27/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) STRAP M/C CABLE AS PER CODE-12" FROM BOX AND PROTECT IN STUD CHANEL 2) PROTECT M/C CABLE WHERE PASSING THROUGH STUD-FHA STRAP 3) FILL UNUSED OPENINGS IN BOXES 4) TIGHTEN LOOSE CONDUIT FITTINGS 5) SUPPORT BOXES ABOVE CEILING 6) FIXTURES TO BE ATTACHED TO GRID AND EXIT SIGN TO HAVE SUPPORT WIRES |