Permit: T03CM02733

Parcel: 13316031C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/31/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/16/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK RECEPTION COUNTER WALL 2) OK ABOVE CEILING PHASE 1
07/15/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0935*/ 1) NO WORK PROGRESS-A REFEE HAS BEEN ASSESSED 2) WALL ELECTRIC NOT SUPPORTED
06/30/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS PHASE ONE-EAST HALF
06/27/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) STRAP M/C CABLE AS PER CODE-12" FROM BOX AND PROTECT IN STUD CHANEL 2) PROTECT M/C CABLE WHERE PASSING THROUGH STUD-FHA STRAP 3) FILL UNUSED OPENINGS IN BOXES 4) TIGHTEN LOOSE CONDUIT FITTINGS 5) SUPPORT BOXES ABOVE CEILING 6) FIXTURES TO BE ATTACHED TO GRID AND EXIT SIGN TO HAVE SUPPORT WIRES