Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* FINISH ITEM#1 OF INSPECTION DATED 6/27/03. CONTRACTOR STATED HE WAS GOING TO TAKE CARE OF THAT ITEM ON 6/27/03. ITEMS 2 & 3 APPROVED |
| 07/03/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/01/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SPACE IS OCCUPIED. ACCESS TO AREA OF WALL FOR INSPECTION IS DIFFICULT. WE HAVE NO WORK PROGRESS SINCE LAST INSPECTION. A REFEE MAY BE ASSESSED |
| 06/27/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PLEASE PROTECT VDV CABLE OUT OF COLUMNS FROM PHYSICAL DAMAGE 2) USE APPROVED FLOOR BOX COVERS AND TIGHTEN LOOSE FITTINGS 3) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370.20 |