Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/04/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/31/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CORRECTIONS MADE-OK 2) OK TO COVER WALLS 3) CLOSET FLANGES NEED TO BE SECURED TO THE FLOOR |
| 07/30/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) DO NOT COVER 2) WHERE IS THE IW PIPING FOR P-5 3) WASTE PIPING MAY NOT BE TIED INTO A VENT (EWC) 4) ALL HORIZONTAL WASTE PIPING TO BE SUPPORTED PER TABLE 3-1 94 UPC |
| 07/28/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* 1) PRESSURE TEST ON WATER OK. 2) WATER TEST ON DRAIN OK. 3) WATER STUB OUTS TO P-5 & P-6 RETATED 90o FROM PLAN (LOCATED) INEAST RATHER THAN NORTH WALL. 4) STUB OUTS? INTO ROOM NORTH OF P-6 DELETED. 5) OK TO COVER. |