Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM02729
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2003 | ELECTRIC - INTERMEDIATE | Approved | ||
07/31/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*/ 1) ELECTRICAL CONTRACTOR REFUSED TO COMPLY WITH NEC ART.300 AND 310 REGARDING BUNDLING OF MC CABLES. REFEE ASSESSED (REMOVED REFEE PER SLONG ON 8/5/03) | |
07/30/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245$/ SEE NOTES BELOW: 1) DO NOT BUNDLE CABLES-IF BUNDLED YOU MUST SUBMIT DERATING FACTORS AND CALCULATIONS AND RESIZE CABLE ACCORDINGLY 2) DO NOT USE NYLON TY-RAPS TO BUNDLE OR SUPPORT CABLE. THESE ARE NOT APPROVED BY CODE OR MANUFACTURER 3) BE SURE YOUR CIRCUITS ARE INSTALLED PER PLAN | |
07/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ PVC UNDERSLAB, THANKS. BE SURE YOU HAVE ENOUGH CODUITS FOR THE NUMBER OF CIRCUITS TO BE COMBINED IN THE RUN. THANKS. |