Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/29/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES 2) ALL ELECTRIC BOXES MUST BE ACCESSIBLE 3) GROUND ALL METAL ELECTRIC BOXES 4) ELECTRIC OUTLET BELOW 8 FEET MUST BE GFCI PROTECTED 5) SECURE OUTLET BOX TO WALL |