Permit: T03CM02720

Parcel: 118272420


Addresses:

1300 S BISON DR


Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T03CM02720

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2004 ROOF NAILING Approved IVRS - Inspection :*
12/06/2004 ROOF NAILING Partial Approval IVRS - Inspection :*/ 1) OVER FRAME AREA NOT NAILED
11/19/2004 ROOF NAILING Partial Approval IVRS - Inspection :*/ 1) ROOF OVER GARAGE OK
2) HOUSE OVER FRAME OK. BUT SHEATHING OVER THAT AREA NOT NAILED
10/29/2004 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ROOF PANELS MUST BE NAILED MAXIMUM SPACING OF 6" ON CENTER AT ALL SUPPORTED ENDS AND EDGES AND 12" ON CENTER IN FIELD TO TRUSSES BELOW 2) PLYWOOD PANELS MUST BE INSTALLED WITH GRAIN PERPENIDCULAR TO SUPPORTING TRUSSES 3) ROOF PANELS MUST SPAN THREE TRUSSES ( 2 BAYS). REPLACE ALL SMALL PANELS 4) TRUSS CLIPS MUST BE ANILED WITH ALL HOLES FILLED USE H2.5 CLIPS 5) ANCHOR BOLTS REQUIRED WITHIN 12" OF ALL PLATE ENDS AND SPLICES AND EVERY 6 FEET THERE AFTER 6) EXPOSE OVER BUILT FRAME 7) PROVIDE COMPLETE CITY APPROVED PLANS 8) OVER FRAME REQUIRES 2 X 8 VALLEY BOARD