Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 06/25/2004 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) SERVICE PANEL (BRANCH BREAKERS MAXIMUM 90 AMPS). NEED LOAD CALC ON SUB IF CHANGED, PLAN SAYS 81 AMPS 2) PLUG HOLE IN SERVICE BOTTOM 3) NEED ANTI-SIPHON AT HOSE BIBS 4) LOOSE UNLABELED WIRE IN SERVICE (LABEL) 5) SMOKE DETECTORS DON'T GO OFF TOGETHER 6) PAINT VTR'S 7) ADDRESS 8) DELETE STAIR FOR FINAL |