Permit: T03CM02695

Parcel: 141304980

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM02695

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2003 FRAMING Approved IVRS - Inspection 0000*
11/24/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) NO TEST ON DWV'S 2) AS PER TABLE E-3702.1 IRC FLAT CABLES SHALL NOT BE STAPLED ON EDGE (ROMEX) 3) OVERSPAN AT WATER HEATER 4) SEAL ALL MOISTURE BARRIER PENETRATIONS 5) NAIL PENETRATED ROMEX AT LEFT SIDE ENTRY 6) INSULATE BEHIND TUB 7) NAIL PROTECT ALL PLUMBING WITHIN 1 1/2" FROM EDGE OF STUD ON HORIZONTAL AND VERTICAL RUNS 8) GAS PRESSURE AT 2 PSI +, 10 PSI REQUIRED 9) STOPPED INSPECTION TO MANY ITEM RECALL WHEN READY
11/20/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) COMPLETE LATH, NEXT INSPECTION IF NOT CORRECTED WILL REFEE
11/17/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) COMPLETE LATH BEFORE CALLING FOR INTERMEDIATES