Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM02672

Parcel: 128140180


Addresses:

5102 E EASTLAND ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/11/2004 FRAMING Approved IVRS - Inspection :*
12/09/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) THE NON CABIN TIED TOP PLATES AT THE NORTHEAST AND NORTHWEST CORNERS, MUST BE WRAPPED ON THE OUTSIDE WITH COIL STRAP-6 NAILS ON EACH FACE (SOUTHWEST CORNER IS CABIN TIED) 2) NEED RSP4'S (STUD CLIPS) IF THE ENTIRE OUTSIDE IS NOT GOING TO BE SHEATHED 3) WEST WALL-STRAP UPPER VERTICALS DOWN TO THE TOP OF STUDS 4) NEED CEILING SHEETROCK NAILERS ALONG WEST WALL AND SHED WEST WALL 5) NEED COIL STRAPS FROM HEADERS TO KING STUDS 6) NOTE: FRAME DOES NOT GET PASSED UNTIL ALL INTERMEDIATES PASS