Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/22/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK CONNECTIONS TO OLD DISTRIBUTION CENTER 2) OK 4-4" PVC INTO TEP TRANSFORMER 3) OK TRANSFER SWITCH TO ENERGIZE GENERATOR 4) OK CONNECTIONS TO SES FROM TRANSFORMER 5) RECEIVED CHECK #3646 FOR AFTER HOURS INSPECTION |
| 11/21/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/20/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BONDING JUMPERS TO BE SIZED PER 250.102 AND TABLE 250.122 ON LOAD SIDE 2) A SIGN FOR STAND BY EQUIPMENT AS PER 702.8 3) PLEASE PROVIDE LETTER FOR GFI TESTING PER 230.95 4) MEETING WITH CONTRACTOR TO PREPARE FOR AFTER HOURS INSPECTIONS ON 11/22/03 5) MAINTAIN WORKING CLEARANCES PER 110.26 |