Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2003 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 11/22/2003 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000* |
| 10/10/2003 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CONTINUATION OF ALL CONDUITS INTO BUILDING FROM TRANSFER SW TO SES GEAR. (TO DISTRIBUTION) ONLY REMAINING IS CONDUITS INTO TRANSFORMER |
| 10/06/2003 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TRANSFER SWITCH TO SBS 4-4" PVC 2) OK TRANSFER SWITCH TO DISTRIBUTION 4-4" PVC OUT 50' 210 DEGREE 3) OK TRANSFER SWITCH TO GENERATOR 4-4" PVC FINISHED RUNS 4) OK TRANSFER SWITCH TO DISTRIBUTION 2-1 1/2" PVC OUT 30' 210 DEGREE 5) OK TO GENERATOR 1-1 1/2" PVC FINISHED RUN 6) OK SBS TO TEP 4-4' PVC OUT 10' |
| 09/26/2003 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) REPAIR BROKEN PVC CONDUITS NEXT TO STAIR WELL AS PER CODES 2) OK 4-4" AND 2-1 1/2" PVC CONDUITS 10' FROM GENERATOR PAD |
| 09/12/2003 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PVC STUB-OUT CONDUIT FROM UNDER SLAB. |