Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM02639

Parcel: 11708254A


Addresses:

909 S 5TH AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/26/2004 PLUMBING - FINAL Approved IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PLBG FINAL IS OK 2) OK FOR C OF O
02/23/2004 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*/ PLBG FINAL IS OK IN BLDG B ONLY. OK FOR C OF O.
02/20/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) CAN NOT HAVE MORE THAN 1 SLIP JOINT ON TRAP ARM. 2) MUST USE DESANKOS ON ALL TRAP ADPTS.
12/12/2003 PLUMBING - FINAL Partial Approval PLBG FINAL OK FOR BLDG 'A'. OK FOR TEMP C OF O AS PER STEVE LONG.
10/16/2003 PLUMBING - FINAL Partial Approval 1) PLBG FINAL IS OK. 2) OK FOR TEMP C OF O AS PER STEVE LONG.
10/04/2003 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLBG FINAL FOR BLDG 'D' ONLY IS OK. 2) OK FOR C OF O AS PER STEVE LONG.
10/03/2003 PLUMBING - FINAL Partial Approval PLBG FINAL FOR BLDG D ONLY IS OK
10/02/2003 PLUMBING - FINAL Denied 1) GALVANIZED 45 IS NOT A DRAINAGE FITTING - MUST USE DURAM 45 DEGREE. 2) KITCHEN SINK TRAP ARM HAS FERNCO COUPLING UNIT D-5.
10/01/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ CAN ONLY HAVE ONE SCIP JOINT ON TRAP ARM.