Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/27/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection :*/ 1) CLEARANCE BY PHONE TO JEANNE |
| 05/26/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Cancelled |
IVRS - Ri canceled |
| 02/11/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* 1) LABEL SERVICE PANEL. 2) CAD WELD OR SPLICE PER CODE. 3) SECURE FLEX WITHIN 12" OF EACH END. 4) SUPPORT CONDUIT AT TOP OF SERVICE. 5) INSTALL DRIP LEG @ FURNACE, WATER HEATER. 6) INSTALL ROOF OUTLET. |
| 09/29/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) RISER NOT INSTALLED 2) CAN NOT SECURED AT STRUCTURE 3) NEEDS TO COORDINATE WITH TEP, ELECTRICIAN, AND INSPECTOR DUE TO METER LOCATION |
| 09/10/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |