Inspection History: PLUMBING - FINAL
Permit Number - T03CM02615
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. | |
10/15/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PLEASE PROVIDE CLEAN OUT AT PREP SINK FOR OVER 135 DEGREE CHANGE OF DIRECTION. 2) DRAINS AT ICE MACHINE MUST BE SEPARATE. 3) ALL DRAINS MUST HAVE INSULATION AT HANDICAP LAVS. | |
10/08/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) PLEASE PROVIDE PROPER APPROVED FLEX FOR GAS AT WOK AND PROPER RESTRAINT FOR FIXTURES WITH GAS CONNECTIONS AND WHEELS. 2) PLEASE PROVIDE RIGHT - LEFT NIPPLE AND COUPLING IN PLACE OF UNION AT ANSUL GAS VALVE. 3) PLEASE PROVIDE PROPER AIR GAP AT INDIRECT DRAIN FROM WOK. 4) PLEASE PROVIDE CLEAN OUT AT ALL DRAINS IN EXCESS OF 135: 5) PLEASE NOTE # 25 ON PLAN. 6) PLEASE PROVIDE FLUSH FLOOR CLEAN OUT AT 3 COMP SINK. THIS MAY NOT BE A COMPLETE LIST. |