Permit: T03CM02608

Parcel: 11306107A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/11/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*/ WILL CHECK FINAL TERMINATION OF CONDENSATE DRAIN ON MECH. FINAL. CONFIRMED VERSION OF PLANS.
09/03/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) CONDENSATE TERMINATION WAS APPROVED IN ERROR ON PLANS. YOU CANNOT TERMINATE CONDENSATE INTO A SEWER WASTE VENT. YOU CAN TERMINATE INTO A PLANTER OR DIRT OR INTO AND APPROVED PLUMBING FIXTURE. PROVIDE A REVISION TO PLANS SHOWING AN APPROVED AREA OF DISPOSAL. RECALL FOR INSPECTION