Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/11/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ WILL CHECK FINAL TERMINATION OF CONDENSATE DRAIN ON MECH. FINAL. CONFIRMED VERSION OF PLANS. |
| 09/03/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) CONDENSATE TERMINATION WAS APPROVED IN ERROR ON PLANS. YOU CANNOT TERMINATE CONDENSATE INTO A SEWER WASTE VENT. YOU CAN TERMINATE INTO A PLANTER OR DIRT OR INTO AND APPROVED PLUMBING FIXTURE. PROVIDE A REVISION TO PLANS SHOWING AN APPROVED AREA OF DISPOSAL. RECALL FOR INSPECTION |