Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/07/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/06/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) 12 GAUGE GROUND AND 14 EACH NEUTRAL NOT ALLOWED ON ONE LUG 2) TWO NEUTRALS NOT ALLOWED ON ONE LUG ON NEUTRAL BAR 3) WIRES TRAPPED MANY FIRE BLOCKS AND SHEAR BLOCKS MISSING 4) PLUMBING OUT OF WALL/CEILING BATH 5) STRAP GAS AND WATER LINES, MOVE WATER LINE |
| 08/04/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) VAPOR BARRIER NOT OVERLAPPED 2" AT ELECTRIC PANEL 2) SEAL ALL BREAKS IN VAPOR BARRIER 3) NO DWV WATER TEST 4) NO TRUSS BRACING 5) BLOCK DUCT BOOTS 6) STUBBED TRUSS NOT BLOCKED TWO SIDES 7) STOPPED INSPECTION, TO MANY ITEMS |