Permit: T03CM02578

Parcel: 106120700

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T03CM02578

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2003 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
06/13/2003 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*/ 1) ATTACH ALL GROUND WIRES 2) TOGETHER IN INTERIOR PANEL AND TO GROUND LINE
06/10/2003 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*/ 1) PRESSURE GUAGE AT 0 PSI. CHECK ALL JOINTS IN SYSTEM 2) UNIT LOCKED. NEED ACCESS TO INTERIOR PANEL 3) COMPLETE GROUNDING AT METER PANEL 4) A REFEE WILL BE ASSESSED IF NOT READY AT NEXT INSPECTION
06/09/2003 ELECTRIC - RECONNECT Denied 2070-90 ALL GROUND WIRES IN INTERIOR PANEL MUST BE CONNECTED TO THE GROUND LUG ON THE LEFT SIDE OF THE FUSES. IT IS MARKED FOR EQUIPMENT GROUND ONLY